In accordance with the poweer delegated to the undersigned
in respect of relaxation of the conditions of supply,
the following relaxation are hereby approved in respect
of conditions 13 and 20 of the conditions of supply
of the Board which should be followed hereafter.
The
condition No. 13 (6) for providing OCI3 by H.T. consumers
has been relaxed as follows:
1. For
a load upto 500 WA the consumer may use fast acting
expulsion type D.O. cutouts with fast acting fuse
elements alongwith A.B. switch which shall be subject
to approval by Board's Engineer.
2. For a load of more than 500 WA
and upto and including 1,000 WA on 11 W the consumers
need upto & including 1,500 WA on 22/33 We need
not provide an O.C.B., but the should provide high
rupturing capacity
fuses of prescribed grade and quality and A.B. switch
on H.T. side.
The
condition No.20 (a) (v) for providing metering equipment
has been relaxed as follows:
For
loads upto and including 500 WA, the metering may
be done on L.T. side.
All
the field officers are requested to note the above
relaxations for future guidance.
|