13.
Consumer's apparatus :
a) Low Tension Consumers:
In the case of
low tension consumer, the consumer must in all cases provide
linked quick-break mains switches and/main fuse on each pole
other than the earthed neutral, which must be erected within
one meter of the Board's meter board or in such other position
as shall be approved by the Board.
b) High Tension Consumers:
In the case of high tension consumers
1) For loads upto 1000 KVA the consumer shall provide fast
acting expulsion type D.O. cutout with fast acting fuse elements
alongwith Air Break switch which shall be subject to approval
by Board's Engineer.
2) For a load of more than 1000 KVA and upto & including
2000 KVA on 11 KV & upto and including 3000 KVA on 22/23
KV, the consumers need not provide an O.C.B. but should provide
high rupturing capacity fuses of prescribed grade and quality
and A.B. Switch on H.T. side.
3) 1 n all other cases suitable circuit breakers must be installed
on the supply side fitted with automatic overload protective
devices so adjusted that they operate before the overload
protective devices in the Board's terminal cubical and further
must be of sufficient rupturing capacity to be specified by
the Board to protect consumer's installations under short
circuit conditions.
In either case, suitable automatic
circuit breakers of a make approved by the Board must be installed
on the low tension side of the transformers or on each feeder.
|