|
15.
Inspection and testing :
a) Low Tension Consumers:
i) Upon receipt of the test report, the Board shall notify
to the consumer the time an day when the Board's representative
proposes to inspect and test the installation. will then be
the duty of the consumers to arrange that a representative
of the wirin contractor employed by him, is present at the
inspection to give the Board or it representative any information
required by him, concerning the installation.
ii) No connection shall be made until the consumer's installation
has been inspecte and tested by the Board and found satisfactory.
No charge shall be made for the fir test by the Board but
subsequent tests due to fault found at the initial test or
failut of the contractor's representative to keep the appointment
as indicated in sut paragraph (i) shall be charged for an
accordance with the schedule of service ar miscellaneous charges
for the time being in force. The Board does not accel responsibility
with regard to the maintenance or testing of wiring on the
consumer premises.
iii)
Before taking the insulation test of the installation the
wiring must be complete in every respect. All fittings such
as lamps, fans, cookers, motors, etc. must be connected up,
fuses inserted and all switches switched in 'ON' position
before the tests are carried out.Temporary wires of fittingsordead
enclsshould not be included in the installation and no part
of the work should be left incomplete. The insulation resistance
of the entire installation to earth shall be tested from the
installation side of the Board's terminals.
iv) The Board shall not connect the conductors and fittings
on the consumer's premises with its works unless it is reasonably
satisfied that the connection will not at the time of making
connection cause a leakage from those conductors and fittings
exceeding one-five thousandth part of maximum supply demanded
on the consumer's premises.
v) A pressure of 500 volts will be applied between the whole
installation and earth and the insulation resistance after
one minute's electrifucation shall not be less than the total
number of Ohms arrived at by dividing the number 10,000,000
in the dry season and 5,000,000 in the rainy season by the
number expressing the maximum electric current in amperes
required.
vi) The test between the poles should give at least half the
result of that to "earth".
vii) In the case of reconnection of supply after a period
of six months or more the consumer shall submit a test report
of the Licensed Electricl Contractor before the supply is
reconnected.
b) High Tension Consumers:
In the case of High Tension Consumers "
i) All Low Tension wiring and equipment will be tested in
accordance with the foregoing conditions.
ii) Manufacturer's test certificates in respect of all H.T.
apparatus shall be produced, if required.
iii) In addition, the Board may test the H.T. installation
by applying standard test voltage in accordance with Indian
Electricity Rules.
|