29.

A.C. system :

*a)

Single phase - 2 wire 230 volts.

 
i)

General supply not exceeding 5 KW connected load.

ii)

Motive power installation not exceeding 1 H. R in aggregate.

b)

Three phase - 4 wire 400 volts between phases and 230 volts between phase and neutral general supply exceeding 5 KW connected load.

c)

Three phase, 3 wire, 400 volts between phase - Motive power installations exceeding 1 H. R in the aggregate.

*d)

Voltage level to be adopted for serving various quantum of loads shall be as under.


 

 

Total Load

Voltage Level

1.

Above 67.5 HP but upto
1500 KVA 11 KV/22 KV :

11KV/22KV

2.

i) Above 1500 KVA but
   upto 3000 KVA :

at 22KV if 33 KV system does
not exist in the area

 

ii) Above 1500 KVA but
    upto 5000KVA 

33 KV

3)

Above 5000 KVA

E.H.V.

Note : The above classification is for the arrangement or grouping of consumer's wiring and not for determining the size of the service line.